Flexible SCADA Help
Data

Protocols

The channel settings of every protocol and how a variable address is written. Fields and options are exactly as in the program windows; the “default” value is filled in by itself and can be left alone.

ProtocolPortDevices
Modbus TCP502PLCs, frequency converters, meters, I/O modules
OPC UA4840OPC UA servers: S7-1500, CODESYS, Beckhoff, Kepware
Siemens S7102S7-300/400/1200/1500, ET200SP, LOGO! 8, S7-200 SMART
IEC 60870-5-1042404telecontrol, protection relays, substation controllers
MQTT1883 / 8883IoT sensors, gateways, Sparkplug B
SNMP161switches, UPSs, air conditioners, PDUs
BACnet/IP47808building controllers
Omron FINS9600Omron CS, CJ, CP, NJ, NX
Mitsubishi MC (3E)5000MELSEC Q, L, iQ-R, iQ-F
EtherNet/IP44818Allen-Bradley Logix, Micro800
KNX IP3671building automation
HTTP (JSON)443 / 80web services: weather, prices, IIoT clouds, equipment REST APIs
Simulator—values by formulas, no device

Common to all channels

Modbus TCP

Modbus TCP is the most widespread protocol of PLCs, frequency converters, meters and I/O modules. Flexible SCADA is the client (master): it reads registers and coils, neighbouring addresses in one request.

The Modbus TCP channel window.
The Modbus TCP channel window.
The window of a Modbus TCP channel variable.
The window of a Modbus TCP channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 502 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Unit IDnumber 1 · defaultslave address, 0…255
Polling period, msnumber 250 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Merging blocks, registersnumber 8 · defaultgap still read in one request
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.

Variable address

ParameterValuesMeaning
AreaHolding Registers (4x) — read/write · defaultInput Registers (3x) — read onlyCoils (0x) — discrete, read/writeDiscrete Inputs (1x) — discrete, read only
Addressnumber 0 · defaultModicon 40001
Unit IDnumber Empty — same as the channel.
Data typeuint16 — unsigned word (WORD) · defaultint16 — signed word (INT)uint32 — 2 registers (DWORD)int32 — 2 registers (DINT)float32 — 2 registers (REAL)float64 — 4 registers (LREAL)bool — bit in a registerHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.
AreaModicon numberWhat it isWritable
Holding Registers4x (40001…)16-bit registers: setpoints, valuesyes
Input Registers3x (30001…)read-only 16-bit registers: measurementsno
Coils0x (00001…)digital outputsyes
Discrete Inputs1x (10001…)digital inputsno

Address — a zero-based number inside the area (the hint next to it shows the Modicon number: Holding address 0 is 40001). Types of 2 and 4 registers are read in a row; the byte order depends on the device: ABCD is the Modbus standard, CDAB — swapped words (common on PLCs), BADC and DCBA — rarer. If a value jumps by orders of magnitude — change the byte order.

OPC UA

OPC UA — a client for OPC UA servers: Siemens S7-1500, CODESYS, Beckhoff, Kepware and others. Values arrive by subscription; beyond the server subscription limit — by reading. Secure connections (Sign, Sign & Encrypt) need mutual certificate trust: the Test connection button shows the server certificate and offers to trust it; the Flexible SCADA certificate for the server is downloaded there too.

The Browse… button in the variable window opens the server address space: pick nodes — variables are created with the NodeId, type and description.

The OPC UA channel window.
The OPC UA channel window.
The window of a OPC UA channel variable.
The window of a OPC UA channel variable.

Channel settings

ParameterValuesMeaning
Connection
Server address (endpoint URL)text e.g. opc.tcp://192.168.0.10:4840opc.tcp://host:port[/path] — as in UaExpert
SecurityNone — no security · defaultBasic256Sha256 · SignBasic256Sha256 · Sign & EncryptAes128_Sha256_RsaOaep · SignAes128_Sha256_RsaOaep · Sign & EncryptAes256_Sha256_RsaPss · SignAes256_Sha256_RsaPss · Sign & EncryptBasic256 · Sign & Encrypt (deprecated)Basic128Rsa15 · Sign & Encrypt (deprecated)
Sign inAnonymous · defaultLogin and password
Publishing interval, msnumber 250 · default
Sampling interval, msnumber how often the server checks the value Empty — same as publishing.
Timeout, msnumber 5000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Value timestampreceive time (recommended) · defaultsource time (PLC clock)OPC UA server time
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
OPC UA protocol settings
Current value polling modesubscription (beyond the server limit — by reading) · defaultread only (cyclic polling)subscription — the server sends changes itself; reading — all values are requested at the polling period
Read polling period, msnumber “read” mode and tags beyond the limit Empty — same as publishing.
Beyond the server's subscription limit — poll by readingcheckbox on · defaultA PLC's subscription item limit is usually shared by the whole server and divided among all clients. Off — tags beyond the limit get status BadTooManyMonitoredItems and the subscription is retried at the resubscribe period.
On-demand subscription: only tags of open screens, scripts and historycheckbox off · defaultThe server monitors only tags of open screens and scripts (UI subscription), and always tags with history (background subscription). When a screen is closed, its tags are removed from the server; other tags are not polled and keep their last value. Helps when a PLC has few subscription items.
Items per subscription, maxnumber beyond — the next subscription Empty — as many as the server accepts.
Nodes per subscription requestnumber
Nodes per read requestnumber
Data filtervalue and quality flag · defaultquality flag onlyvalue, quality and timestampwhat the server considers a change
Value queuenumber 1 · defaultitem values between publications
Resubscribe period, snumber 60 · defaultretry for tags the server did not accept; 0 — do not retry
Subscription timeout, msnumber how long the server keeps a subscription without connection
Session timeout, msnumber 60000 · defaulthow long the server keeps a session after a disconnect

Variable address

ParameterValuesMeaning
NodeIdtext e.g. ns=2;s=Tank.Levelns=3;s="DB1"."Temp" · ns=2;i=1001 · nsu=urn:…;s=… — or pick it in the browser
Typeas the server decides (automatic) · defaultBooleanInt16 / SByteUInt16 / ByteInt32 / EnumerationUInt32Int64UInt64FloatDoubleString / LocalizedText
Sampling interval, msnumber Empty — same as the channel.

Siemens S7

Siemens S7 over ISO-on-TCP: S7-300/400/1200/1500, ET200SP, LOGO! 8, S7-200 SMART. On S7-1200/1500 allow PUT/GET access in the CPU properties and clear “Optimized block access” on the data blocks. A data block can be imported from TIA Portal (a .db source) — variables are created from the block structure.

The Siemens S7 channel window.
The Siemens S7 channel window.
The window of a Siemens S7 channel variable.
The window of a Siemens S7 channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 102 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 250 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
Siemens S7 protocol settings
Racknumber 0 · default0…7
Slotnumber 1 · defaultS7-300: 2, 1200/1500: 1 (or 0)
Connection typePG (programming device) · defaultOP (panel)S7 basic
Merging, bytesnumber 32 · defaultgap read in one block
Own TSAPtext e.g. 0100LOGO! / S7-200: from the PLC settings
PLC TSAPtext Empty — from rack and slot.

Variable address

ParameterValuesMeaning
Addresstext e.g. DB1.DBD0DB1.DBX0.0 · DB1.DBB2 · DB1.DBW4 · DB1.DBD6 · DB1.DBS10.20 (STRING[20]) · M0.1 · MW10 · I0.0 / E0.0 · Q0.0 / A0.0
Data typeby address (X — BOOL, B — BYTE, W — INT, D — REAL) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.
AddressWhat it isDefault type
DB1.DBX0.0bit 0 of byte 0 of data block 1BOOL
DB1.DBB2byte 2BYTE
DB1.DBW4a word (2 bytes) from byte 4INT
DB1.DBD6a double word from byte 6REAL
DB1.DBS10.20a STRING[20] from byte 10STRING
M0.1, MW10markersBOOL / INT
I0.0 / E0.0inputs (read-only)BOOL
Q0.0 / A0.0outputsBOOL

The type is defined by the size letter; for DINT, DWORD, LREAL set the type explicitly.

IEC 60870-5-104

IEC 60870-5-104 — power telecontrol. Flexible SCADA is the controlling station: after connecting it makes a general interrogation, then values arrive spontaneously. Commands are confirmed (ACT_CON), optionally with select-before-operate (SBO).

The IEC 60870-5-104 channel window.
The IEC 60870-5-104 channel window.
The window of a IEC 60870-5-104 channel variable.
The window of a IEC 60870-5-104 channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 2404 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Connection keep-alive, msnumber 250 · defaultThis protocol delivers values by itself; the period only serves connection checks and service traffic.
Timeout, msnumber 2000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
IEC 60870-5-104 protocol settings
Common ASDU addressnumber 1 · defaulta variable can have another (ca)
General interrogation every, snumber 0 · default0 — only on connect
Timestampsreceive time · defaultstation timestamp (UTC)station timestamp (local)
t1, snumber 15 · defaultresponse wait
t3, snumber 20 · defaultTESTFR on silence
wnumber 8 · defaultacknowledge every w
Wait for command confirmation, msnumber 10000 · default
Synchronize the station clock on connectcheckbox off · default

Variable address

ParameterValuesMeaning
Information object address (IOA)number 1 · default1…16777215
Common address (CA)number Empty — same as the channel.
Write commandnone (read only) · defaultsingle C_SC_NA_1double C_DC_NA_1normalized setpoint C_SE_NA_1scaled setpoint C_SE_NB_1floating-point setpoint C_SE_NC_1
Data typefrom the station data · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)How to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

MQTT

MQTT 3.1.1 and 5: IoT sensors, gateways, controllers with MQTT. Values arrive by subscription. The topics mode — a value in the message (“21.5”, “true”) or at a JSON path; the Sparkplug B mode — node metrics by their BIRTH / DATA / DEATH, writing — with a DCMD/NCMD command.

The MQTT channel window.
The MQTT channel window.
The window of a MQTT channel variable.
The window of a MQTT channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 1883 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Connection keep-alive, msnumber 500 · defaultThis protocol delivers values by itself; the period only serves connection checks and service traffic.
Timeout, msnumber 3000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
MQTT protocol settings
Modetopics (value / JSON) · defaultSparkplug B
MQTT version3.1.1 · default5
Client IDtext Empty — random.
Keep alive, snumber 30 · default
Subscription QoS01 · default2
TLS (usually port 8883)checkbox off · default
Clean sessioncheckbox on · default
Login with user name and passwordcheckbox off · defaultThe broker or server requires a login and password; the password is stored in the project encrypted.

Variable address

ParameterValuesMeaning
Topictext e.g. plant/line1/temp
JSON pathtext data.temp · values[0] · $.a.b Empty — empty — the whole message.
Timestamp in JSONtext e.g. tsEmpty — ts.
Write topictext Empty — same as the topic.
Path when writingtext {"data":{"sp":7}} — data.sp Empty — empty — the value as is.
Retain on writecheckbox off · default
Data typenumber (LREAL) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

SNMP

SNMP v1, v2c, v3: switches, UPSs, air conditioners, PDUs. An OID — as a number or a MIB-2 name (sysUpTime.0, ifInOctets.1). v3 — user, authentication and encryption; communities and passwords are encrypted in the project.

The SNMP channel window.
The SNMP channel window.
The window of a SNMP channel variable.
The window of a SNMP channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 161 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 5000 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
SNMP protocol settings
Versionv2c · defaultv1v3
Community (read)text
Community (write)text Empty — same as read.
OIDs per requestnumber 20 · default
Retriesnumber 1 · default

Variable address

ParameterValuesMeaning
OIDtext e.g. 1.3.6.1.2.1.1.3.0or a MIB-2 name: sysUpTime.0, ifInOctets.1, upsOutputPercentLoad.1
Type when writingas read · defaultINTEGERGauge32Counter32TimeTicksOCTET STRINGIpAddress
Data typenumber (LREAL) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

BACnet/IP

BACnet/IP — building controllers (UDP 47808): reading with ReadPropertyMultiple, present-value together with status-flags (a fault gives Uncertain quality); writing — with a priority.

The BACnet/IP channel window.
The BACnet/IP channel window.
The window of a BACnet/IP channel variable.
The window of a BACnet/IP channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 47808 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 1000 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
BACnet/IP protocol settings
Device numbernumber Empty — any.
Write prioritynumber 8 · default1…16; 8 — operator
Objects per requestnumber 20 · default
Network (DNET)number device behind an MS/TP router Empty — no.
Own IP addresstext on a PC with several networks — the address in the device network Empty — auto.
Own UDP portnumber 0 · default0 — any; 47808 — if the device answers only on it
Retriesnumber 1 · default
Read status-flags (fault → Uncertain)checkbox on · default

Variable address

ParameterValuesMeaning
Objecttext e.g. AI:1AI, AO, AV, BI, BO, BV, MSI, MSO, MSV, IV, CSV, DEV — and a number
Propertytext e.g. present-valueobject-name, status-flags, units… or a number Empty — present-value.
Indexnumber Empty — —.
Prioritynumber Empty — channel.
Data typeby object (BI/BO/BV — BOOL, MS* — number) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

Omron FINS

Omron FINS over TCP or UDP: CS, CJ, CP, NJ, NX. 32-bit values — the low word at the lower address.

The Omron FINS channel window.
The Omron FINS channel window.
The window of a Omron FINS channel variable.
The window of a Omron FINS channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 9600 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 250 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
Omron FINS protocol settings
TransportFINS/TCP · defaultFINS/UDP
PLC node (DA1)number Empty — auto.
Own node (SA1)number Empty — auto.
Network (DNA)number 0 · default
Words per requestnumber 500 · default
Merging, wordsnumber 16 · default

Variable address

ParameterValuesMeaning
Addresstext e.g. D100D100 · D100.05 · CIO10 / 10.03 · W3 · H5 · A100 · E0_100 · T5 · C5
Data typeby address (bit — BOOL, word — INT) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

Mitsubishi MC (3E)

Mitsubishi MC protocol, 3E frame, binary code: MELSEC Q, L, iQ-R, iQ-F (FX5). In the PLC open an MC protocol port (TCP), choose “binary code” and allow writing in RUN.

The Mitsubishi MC (3E) channel window.
The Mitsubishi MC (3E) channel window.
The window of a Mitsubishi MC (3E) channel variable.
The window of a Mitsubishi MC (3E) channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 5000 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 250 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
Mitsubishi MC (3E) protocol settings
SeriesQ / L / iQ-R (X, Y — hex) · defaultiQ-F FX5 (X, Y — octal)
Networknumber 0 · default
Station (PC)number 255 · default
Words per requestnumber 480 · default
Merging, wordsnumber 16 · default

Variable address

ParameterValuesMeaning
Devicetext e.g. D100D100 · D100.F · W1A · R0 · ZR10 · SD0 · TN5 · M100 · X1F · Y20 · B0 · SM400
Data typeby address (bit — BOOL, word — INT) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

EtherNet/IP (Logix)

EtherNet/IP (CIP) — Allen-Bradley ControlLogix, CompactLogix, GuardLogix, Micro800: tags by name, as in Studio 5000. ControlLogix — a route through the backplane and the CPU slot.

The EtherNet/IP (Logix) channel window.
The EtherNet/IP (Logix) channel window.
The window of a EtherNet/IP (Logix) channel variable.
The window of a EtherNet/IP (Logix) channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 44818 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Polling period, msnumber 250 · defaultHow often to read all variables of the channel. Smaller — fresher values, but more load on the network and the PLC.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
EtherNet/IP (Logix) protocol settings
Routebackplane → slot · defaultdirect (CompactLogix, Micro800)
CPU slotnumber 0 · default
Bytes per requestnumber 480 · defaultread batch size

Variable address

ParameterValuesMeaning
Tagtext e.g. Motor.SpeedSpeed · Motor.Speed · Arr[3] · Program:Main.Level · bit — Flags.5
Data typeas the controller decides · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
Scalenumber 1 · defaultEngineering value = raw × scale + offset.
Offsetnumber 0 · defaultAdded after the scale.

KNX IP

KNX IP — building automation through a KNX IP interface or router. Values arrive as bus telegrams; on connecting the groups are read. Group addresses and DPTs are imported from the ETS project (the Import from ETS button). KNX IP Secure and Data Secure are supported (an ETS keyring file). Windows only.

The KNX IP channel window.
The KNX IP channel window.
The window of a KNX IP channel variable.
The window of a KNX IP channel variable.

Channel settings

ParameterValuesMeaning
Connection
IP address or hosttext e.g. 192.168.0.10The device address on the network: 192.168.0.10 or a host name.
Portnumber 3671 · defaultThe TCP or UDP port of the protocol; the default is the protocol standard one (filled in when the driver is chosen).
Connection keep-alive, msnumber 200 · defaultThis protocol delivers values by itself; the period only serves connection checks and service traffic.
Timeout, msnumber 1000 · defaultHow long to wait for an answer. No answer — a communication error and a reconnection.
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.
KNX IP protocol settings
Connectiontunnel (IP interface) · defaultrouting (multicast)
Tunnel transportauto · defaultUDPTCP (KNXnet/IP 2)
Own addresstext tunnel: the gateway tunnel address (1.1.250), routing: the SCADA address on the line (default 15.15.250) Empty — the gateway assigns.
Re-read every, snumber 0 · default0 — do not re-read: values arrive on change
Pause between reads, msnumber 20 · defaultTP bus — 9600 baud: no more than ~40 reads per second
Telegram prioritylow (normal) · defaulthighalarm
ETS keyring file (KNX Secure)text e.g. C:\KNX\project.knxkeyspath on the server; needed for KNX IP Secure and Data Secure
Via NAT (gateway behind a router)checkbox off · default
Read groups on connectcheckbox on · default

Variable address

ParameterValuesMeaning
Group addresstext e.g. 1/2/3main/middle/address: 0…31 / 0…7 / 0…255
DPTtext e.g. 9.0011.001 on/off · 5.001 % · 9.001 °C · 14.056 W · 16.000 text · 20.102 mode
Write addresstext command, if the address above is the status (light: 1/1/1 → status 1/1/2) Empty — same as the group address.
Read on connectcheckbox on · default
Data typeby DPT (1.x — BOOL, 9.x — REAL, 16.x — STRING…) · defaultBOOLINT (int16)UINT / WORD (uint16)DINT (int32)UDINT / DWORD (uint32)LINT (int64)ULINT (uint64)REAL (float32)LREAL (float64)STRINGHow to read the value. “By address” — by the size letter or the device data.
DPTWhat it isVariable type
1.001on/offBOOL
5.001percent 0…100REAL
9.001temperature, °CREAL
14.056power, WREAL
16.000textSTRING
20.102heating modeINT

HTTP (JSON) — web services

HTTP (JSON) brings in data from web services: weather, energy prices and rates, IIoT cloud platforms, REST APIs of equipment and building systems. Once per poll period Flexible SCADA requests (GET) the path of each variable and takes the needed field from the JSON response; variables with the same path share one request per cycle. Read-only.

Channel parameters

ParameterWhat to set
IP address or hostthe service address without https://: api.open-meteo.com
Port443 — HTTPS, 80 — HTTP
HTTPS (secure connection)on by default; clear it for a service on http://
Do not verify the service certificatefor a service on the internal network with its own (self-signed) certificate
Key header, Header valuewhen the service expects an API key in a header (Authorization: Bearer …, X-API-Key); the value is encrypted in the project
Poll period, ms5–15 minutes is enough for weather (600 000 ms); at most once a second
Timeout, mshow long to wait for the service to answer

Variable address

FieldWhat it isExample
Request patheverything after the host: path and parameters (a space is %20)/v1/forecast?latitude=55.75&longitude=37.62&current=temperature_2m
Response fieldthe JSON path: names with dots, array items — [0]; empty — the whole responsecurrent.temperature_2m, daily.sunset[0]
Data typea number, a boolean (true/false, 0/1) or a stringSTRING — sunrise time
Scale, offsetunit conversionkm/h → m/s: 1/3.6

Weather without a key: the Open-Meteo service — host api.open-meteo.com, port 443, period 600 000 ms; a variable with the path /v1/forecast?latitude=55.7558&longitude=37.6173&current=temperature_2m and the field current.temperature_2m gives the temperature in Moscow. The “Pine Quarter residential complex” demo project is built this way.

A non-2xx response, a missing field or “not a number” — the variable gets bad quality with the reason in the Status column (response 404, “the response has no field …”); the service does not answer — the channel is “no connection” and reconnects. On a site without internet access the channel is simply offline.

Simulator

Simulator generates signals by formulas — to debug windows, alarms and trends without a device. The functions and their parameters are on the Variables and channels page.

The Simulator channel window.
The Simulator channel window.

Channel settings

ParameterValuesMeaning
Connection
Update period, msnumber 250 · default
Poll the channelcheckbox on · defaultOff — the channel does not connect (during commissioning or repairs); its variables have Bad quality.