Quick start
We will build a tutorial heating-substation project: a circulation pump and a pressure sensor on a window, live values from a simulator, a trend, an alarm on the pump fault, and publish it to the operator. Start the Flexible SCADA application and connect to a server. You can use the development server on the same computer. The simulator supplies the controller data.
1
2
12
1

12
12
12
12
12
12
123
Below are the same steps in detail. Each takes a minute or two; you can build the project while reading.
Step 1. Open the development environment
Open the Flexible SCADA program (the “Flexible SCADA” shortcut) and on the Servers screen click Open IDE next to the server (how to install the server and the IDE — Installation). The development environment opens: the menu bar at the top, the tree on the left, the work area in the middle and the Properties column on the right (details — Development environment).
1Step 2. Create a project
- Right-click the Projects branch and choose New project….
- Enter a name, for example
Heating substation — tutorial, and press OK.
2
GIF
12A project is one .wscada file on the server: channels, variables, windows, objects, programs. It can be exported and imported to another server (File → Export project…), while the running server keeps the archive and the alarm journal alongside it. Details — Projects.
Step 3. Add a simulator channel
A channel is a connection to a device over a protocol: a PLC over Modbus or S7, an OPC UA server and so on. For learning we take the simulator — it generates values by formulas.
- Right-click the project → Create → Channel (protocol) → Simulator.
- Name the channel
SIMand press Add channel. - Press the Save button in the menu bar (or Ctrl+S).
1
GIF
12Changes to channels and variables do not disturb the running server until you press Save: you can safely change many addresses at once. Windows, objects and types are saved immediately by themselves.
Step 4. Create variables
Click the SIM channel — its variable table opens. Add four variables with + Variable:
| Name | Description | Units | Decimals | Function | Amplitude | Offset | Period, s |
|---|---|---|---|---|---|---|---|
SIM.P1.Run | Pump 1 running | 0 | Square wave | 1 | 0 | 60 | |
SIM.P1.Freq | Pump 1 frequency | Hz | 1 | Sine | 5 | 45 | 30 |
SIM.P1.Fault | Pump 1 fault | 0 | Square wave | 1 | 0 | 180 | |
SIM.PT1.P | Supply pressure | bar | 2 | Random walk | 1 | 4 | 10 |
GIF
Variables and channels page." loading="lazy">Press Save — the values come alive: the frequency swings around 45 Hz, the pressure wanders around 4 bar, the fault turns on for a minute and a half every three minutes.
1
Step 5. A window and objects from the library
- Right-click the project → Create → Window → Empty window, name it
Substation. - In the library in the right column search for the circulation pump and double-click its tile — it lands on the window. Give it the object name
CircPump1in Properties. - Place the pressure sensor the same way, name it
PT1and set X = 260, Y = 60 in Properties (or simply drag it with the mouse).
1
12
GIF
12The pump on the window is not just a picture but a project object: it has its own variables (Run, Freq, Fault), windows and alarms, described once in the library type. Change the type — and every pump of the project changes. Details — Objects and types.
Step 6. Bind the object variables
Select the pump — in Properties, in the Variable bindings section, every object variable has a field. Type in (or drag from the tree) the channel variables:
| Object | Object variable | Source | Bind to |
|---|---|---|---|
| CircPump1 | Run | tag | SIM.P1.Run |
Freq | tag | SIM.P1.Freq | |
Fault | tag | SIM.P1.Fault | |
| PT1 | P | tag | SIM.PT1.P |
Flow | value | 1 — there is always flow |
12
Press Save. An object variable without a binding takes its default value from the type.
GIFStep 7. Watch it run
The Editing button in the window header switches it to running: elements no longer get selected, buttons can be pressed, values are live — exactly what the operator will see.
12
GIFStep 8. A trend of frequency and pressure
- Right-click the project → Create → Trend → Trend (set of variables), name it
Pump 1. - Expand the
SIMchannel in the tree and drag theFreqandPvariables onto the trend row. - The trend asks whether to write them to the archive — press Turn on archive and then Save: the trend will then show the past too, not only new values.
1
12
GIF
Trends." loading="lazy">12Step 9. An alarm on the pump fault
- Right-click the project → Create → Alarm.
- Variable —
SIM.P1.Fault, kind — digital: on (≠ 0), priority — 2 — High, area —Substation, message —Circulation pump 1 fault. - Fill in the operator guidance: cause, consequence and action — the operator sees them by clicking the alarm. Press Add.
1
Alarms page." loading="lazy">
GIF
1When the fault turns on, an alarm bar appears in the header; clicking it opens Active, where the alarm is acknowledged.
12Step 10. Publish for operators
Operators see not the draft but the published version of the windows — so an unfinished change never reaches their screens. The Publish button in the menu bar (1) opens publishing: what changed, a link check, the version comment (2) and the Publish version 1 button (3).
GIF
123
Publishing." loading="lazy">Step 11. The operator client
Open the operator screen — the server address in a browser (http://localhost:5080) or Operator next to the server in the Flexible SCADA program. This is the dispatcher's workstation: the start window right away, a narrow bar at the top (⌂ ← ↑, alarms, reports, time), the alarm bar with sound at the bottom. The pump shows the fault sign; clicking it opens its panel.

What next
- Connect a real controller — Protocols: Modbus TCP, OPC UA, S7 and others.
- Draw a mimic diagram — Window editor and Window elements: pipes with flow, buttons, indicators.
- Make your own equipment type — Objects and types.
- Add logic — Programs; reports — Reports; users and roles — Administration.